SecuriFire 2000

FeaturesOperation/DescriptionsSpecifications
  • Lightning-fast detection of incipient fires
  • Modular and decentralised architecture
  • Up to 4 addressable loops (totalling 14,000 m) with up to 1,000 elements per system
  • Fully redundant software design for permanent availability
  • Simple planning and programming
  • Backward and forward compatible
  • Cost-efficient solutions
  • Complies with the highest safety standards
  • Interfaces to the outside and to superordinate systems
  • Compact design

The compact SecuriFire 2000 fire alarm control panel controls the system components and evaluates the detector data, either centralised or decentralised in the control panels networked in the SecuriLan. The detectors, the wide range of different input/output modules and the special detectors communicate directly with the control panel via the SecuriLineeXtended. Even already installed Securiton detectors can be integrated into a SecuriFire system problem-free. Thanks to the system design, SecuriFire 2000 is also tested and approved as a control panel for single-zone extinguishing systems (EN 12094-1 compliant).

Technical data SCP-20XX  
230 VAC +15%/-20% Mains voltage
47-63 Hz Frequency
160W Power consumption max.
4A Output current
12V/17Ah Batteries (largest): 2 pieces in series
IP 30 Protection class
-5°/+50°C Ambient temperature
26.3 VDC (+50°C) - 28.3 VDC (0°C) Output voltage
74mA Quiescent current (w/o oper. panel, w/o printer)
5-95% Rel. air humidity: without condensation
400×445×150 mm/8kg Dimensions (H×W×D)/Weight of basic version (without batteries)

 

Technical data SecuriLineeXtended  
250max./Automatic Number of addresses
3500m Ring circuit length
531 Backwards compatibility to series
> 300 mA Short-circuit detection
24 VDC Rated operating voltage
-4 SecuriLineeXtended
< 100sec. Starting/repairing time

 

Technical data SecuriLan  
RS 485, TCP/IP Bus technology
2500 kBit/s Data transfer
32 max. Number of participants on the SecuriLan
16 max./31 max. Number of centrals/Number of external operating panels
24 VDC Rated operating voltage
Cat 5 UTP RS 485 Cable (without power supply
1.2 km max. Length, between 2 participants
62.5/125 µm Cable (without power supply)
50/125 µm Multimode/MTRJ
2 km max./10 km max. Length, Multimode/Length, Singlemode
9/125 µm Cable (without power supply), Singlemode/LC 2×5

 

Product summary  
B6-SCP2010 SecuriFire 2000 basic version
B6-SCP2020 SecuriFire 2000 basic version, with built-in operating panel MIC11
B6-SCP2030 SecuriFire 2000 basic version, with built-in operating panel MIC11 and printer
B6-SCP2040 SecuriFire 2000 basic version, with built-in operating panel MIC11, printer and cut-out for EPI devices or Ext. Zone panel
B6-SCP2050 SecuriFire 2000 basic version, with built-in operating panel MIC11 and control map and cut-out for EPI device or one-sector extinguishing display

SecuriFire 1000

FeaturesOperation/DescriptionsSpecifications
  • Lightning-fast detection of incipient fires
  • Up to 250 detectors and other elements per system
  • Addressable loop up to 3,500 m in length
  • Fully redundant software design for permanent availability
  • Simple planning, programming and operation
  • Backward and forward compatible
  • Cost-efficient solutions
  • Complies with the highest safety standards
  • Interface for connection to the fire services
  • Compact design

The compact SecuriFire 1000 fire alarm control panel controls the system components and evaluates the detector data. The detectors, the wide range of different input/output modules and the special detectors communicate directly with the control panel via the SecuriLineeXtended.

Technical data SCP-10XX  
230 VAC +15%/-20% Mains voltage
47-63 Hz Frequency
160W Power consumption max.
4A Output current
12V/17Ah Batteries (largest): 2 pieces in series
IP 30 Protection class
-5°/+50°C Ambient temperature
26.3 VDC (+50°C) - 28.3 VDC (0°C) Output voltage
74mA Quiescent current (w/o oper. panel, w/o printer)
5-95% Rel. air humidity: without condensation
400×445×150 mm Dimensions (H × W × D)
8 kg Weight of basic version: (without batteries)

 

Technical data SecuriLineeXtended  
250max. Number of addresses
3500m Ring circuit length
Automatic Address allocation
531 Backwards compatibility to series
> 300 mA Short-circuit detection
24 VDC Rated operating voltage
Loop Type of laying
< 100sec. Starting/repairing time

 

Product summary  
B6-SCP1020 SecuriFire 1000 basic version, with built-in operating panel
B6-SCP1030 SecuriFire 1000 basic version, with built-in operating panel and printer

SecuriFire 3000

FeaturesOperation/DescriptionsSpecifications
  • Lightning-fast detection of incipient fires
  • Fully redundant hardware and software design
  • Modular and decentralised architecture
  • Up to 16 ring circuits with 3,500 elements per control unit
  • Data interfaces to the outside and to higher level systems
  • Simple planning, programming and operation
  • Highest security standards

The SecuriFire fire alarm system is a modular, decentralised fire alarm system consisting of individual components and can be adapted to individual system requirements. The SecuriFire 3000 fire alarm control panel controls the system components and evaluates the detector data, either centralised or decentralised in the control panels networked in the SecuriLan. The detectors, the wide range of different input/ output modules and the special detectors communicate directly with the control panel via the SecuriLineeXtended. Even already installed Securiton detectors can be integrated into a SecuriFiresystem problem-free. Thanks to the system design, SecuriFire 3000 is also tested and approved as a control panel for multi-zone extinguishing systems (EN 12094-1 compliant).

Technical data SCP-20XX  
230 VAC +15%/-20% Mains voltage
47-63 Hz Frequency
350W Power consumption max.
7A Output current
12V/45Ah Batteries (largest): 2 pieces in series
IP 30 Protection class
0°/+50°C Ambient temperature
26.3 VDC (+50°C) - 28.3 VDC (0°C) Output voltage
97mA Quiescent current (w/o oper. panel, w/o printer)
5-95% Rel. air humidity: without condensation
670×470×230 mm/23.5kg Dimensions (H×W×D)/Weight of basic version (without batteries)

 

Technical data SecuriLineeXtended  
250max./Automatic Number of addresses/Address allocation
3500m Ring circuit length
531 Backwards compatibility to series
> 300 mA Short-circuit detection
24 VDC Rated operating voltage
12 VDC/24 VDC Rated voltage auxiliary power supply
-16 SecuriLineeXtended
< 100sec. Starting/repairing time

 

Technical data SecuriLan  
RS 485, TCP/IP Bus technology
2500 kbit/s Data transfer
32 max. Number of participants on the SecuriLan
16 max./31 max. Number of centrals/Number of external operating panels
24 VDC Rated operating voltage
Cat 5 UTP RS 485 Cable (without power supply
1.2 km max. Length, between 2 participants
62.5/125 µm Cable (without power supply)
50/125 µm Multimode/MTRJ
2 km max./10 km max. Length, Multimode/Length, Singlemode
9/125 µm Cable (without power supply), Singlemode/LC 2×5

 

Product summary  
B5-SCP3010 SecuriFire 3000 basic version
B5-SCP3020 SecuriFire 3000 basic version, with built-in operating panel MIC11
B5-SCP3030 SecuriFire 3000 basic version, with built-in operating panel MIC11 and printer
B5-SCP3040 SecuriFire 3000 basic version, with built-in operating panel MIC11, printer and cut out for EPI devices
B6-SCP3050 SecuriFire 3000 basic version, with built-in operating panel MIC11 main indication and control map, protocol printer and cut-out for MMI device

SecuriFire 500

FeaturesOperation/DescriptionsSpecifications
  • Lightning-fast detection of incipient fires
  • Easy to operate on site and remotely
  • Quick and easy to configure and program
  • Data transmission using state-of-the-art IP technology
  • Interface for connection to the fire services
  • VdS approval in compliance with EN 54-2, EN 54-4 and EN 54-13; complies with all Cantonal Fire Insurance Union and SES norms
  • Compatible with existing and future generations of detectors

The compact SecuriFire 500 fire alarm control panel controls the system components and evaluates detector data. The detectors, the wide range of different input/output modules, and the special detectors communicate directly with the control panel via the SecuriLineeXtended.

Technical data SCP 500  
110/230 VAC +15%/-20% (47-63 Hz) Mains voltage
75 W Max. power consumption
2,5 A Output current
12 V/7 Ah Batteries (largest): 2 pcs. in series
IP 30 Protection class
-5°/+50°C Ambient temperature
26,3 V DC (+50 °C) - 28,3 V DC (0 °C) Output voltage
5-95% Rel. air humidity, without condensation
300 × 360 × 80 Dimensions (H × W × D)
2,3 kg Weight of basic version (without batteries)
10 000 Event memory «events on board»

 

Technical data SecuriLineeXtended  
250max. Number of addresses
3500m Addressable loop length
Automatic Address allocation
531 Backwards compatibility to series
> 300 mA Short-circuit detection
24 VDC Rated operating voltage
Ring/Loop Type of conveyance

 

Product summary  
B7-SCP 520 SecuriFire 500 with operating panel

PHOTO GALLERY